Categories Electric Heat Tracing
Brand Name: MICH
Model Number: MICHTHMM
Certification: ISO9001
Place of Origin: China
MOQ: 1 meter
Price: USD0.5-USD5 per meter
Supply Ability: 10 million meters per year
Delivery Time: in one month
Packaging Details: plywood crates
Conductor: Copper
Sheath: Copper-Nickel
Insulation: Magnesium Oxide
Usage: Mine and Minerals
Min. Bend Radius: 6 X Cable Diameter
Max. Maintenance Temp. (°F): 900
Max. Exposure Temp. (°F) Power Off: 1100
ApplicatioMaterial and measurement Pipelinesns: process equipment and piping
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Mineral Insulated Heating Cable In Mine And Minerals

Mineral Insulated Heating Cable and Heater for Heat Trace and Heater in Mine and Minerals is a solution system to provide freeze protection and counteracts heat loss from process equipment and piping, and prevents increase of product viscosity. Pasia is capable of providing complete line of heat trace cable and installation kits.


Cable Structure


Specification

Heating cable instruction code


MI CU-B 16K320/60/2520/220/E1

No. 1 2 3 4 5 6 7


No.Instruction
1Sheath materialCU
2structure of cable componentsshown in table 1
3cable codesshown in table 2, 3 and 4
4length of heating cableIn meter
5Heating cable powerIn Watt
6heating cable voltageIn Volt
7heating cable voltageSee table 5

Cable Code


1 6 K 320

No. 1 2 3 4


Serial NO.Instruction
1core number1 or 2
2Voltage grade3=300V, 6=600V
3conductor materialsC,K
4cold resistance ×1000320=0.32Ω/m×1000

Table 1 Structure of Cable Element


Note: Model C, F and G are suitable for being used at temperature under 65


Table 2 Heating Cable Specification (600V Single Conductor)


Cable CodeDiameterHDPE DiameterStandard resistance value at +20Maximum Production LengthUnit weight
mmmmΩ/mmkg/km
16C1.78.2100.0017350366.54
16C2.27.69.40.0022380307.77
16C2.97.08.80.0029400264.45
16C45.97.70.004600190.88
16C75.37.10.007600154.08
16C114.96.70.011600132.25
16C134.66.40.013600 (300)☆125.7
16C174.66.40.017600 (300)☆117.16
16C214.66.40.021600 (300)☆111.9
16C253.75.50.025600 (480)☆68.83
16C333.75.50.033600 (480)☆63.76
16C403.45.20.04600 (560)☆58.87
16C633.250.06360051.47
16K806.88.60.08370 (140)☆254.18
16K1005.270.1450 (240)☆162.11
16K1404.96.70.14600 (270)☆122.55
16K1974.456.250.197600 (330)☆111.32
16K2204.56.30.22600 (330)☆102.89
16K3154.36.10.315600 (350)☆91.44
16K3454.26.00.345600 (370)☆85.9
16K4504.05.80.45600 (400)☆80.73
16K6304.05.80.63600 (400)☆77.26
16K8003.55.30.8600 (530)☆61.48
16K12502.84.61.2560040.83
16K20002.84.62.060038.96

Table 3 Heating Cable Specification (600V Double Conductors)


Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
26C3.412.90.0034150783.76
26C4.412.20.0044160701.56
26C5.811.30.0058170606.16
26C8.69.900.0086180451.43
26C11.49.300.0114200400.05
26C13.89.000.0138210375.20
26C17.28.600.0172220344.90
26C238.000.023250303.25
26C34.47.500.0344280269.20
26C49.27.100.0492300243.84
26K2409.900.24180451.43
26K3209.300.32200400.05
26K3849.000.384210375.20
26K4808.600.48220344.90
26K6408.000.64250303.25
26K9607.500.96280269.20

Table 4 Heating Cable Specification (300V Double Cores)


Cable CodeDiameterNominal resistance at +20Maximum manufacturing lengthUnit weight
mmΩ/mmkg/km
23C3.412.00.0034200708.10
23C4.411.30.0044220629.07
23C5.810.40.0058240537.73
23C8.69.000.0086260392.56
23C11.48.400.0114280343.89
23C13.88.000.0138300314.57
23C17.27.600.0172320286.27
23C237.100.023340252.98
23C34.46.600.0344360221.19
23C49.26.200.0492380197.64
23K16010.40.16220508.37
23K2409.000.24240392.56
23K3208.400.32265343.89
23K3848.000.384280314.57
23K4807.700.48300291.91
23K6407.100.64320252.98
23K9606.500.96350216.11

Note: the resistance value of 2-core cable in the above table is the measured value after the ends are twisted (i.e., single-core resistance X2);

For the use of 660V voltage occasions, please contact our company professionals;

Mark of (300)☆ is a recommended production length by MICH


Table 5 terminal specifications


Model: A, D, EModel: B
Maximum Voltage(V)Maximum Current (A)Terminal SpecificationMaximum Voltage(V)Maximum Current (A)Terminal SpecificationMaximum Voltage(V)
60015E220E115E1
60020E225E220E1
60030E340E230E2
60050E370E250E2
60070E3100E370E2

Note 1: E1 means 1/2 "NPT;E2 means 3/4 "NPT;E3 represents 1 "NPT (taper thread);Additional connection thread requirements are available.

Note 2: the length of cold end cable with standard configuration is 2 meters. If you increase or decrease of length required, please contact our professional personnel.


Corresponding reference table between the output power and sheath temperature