Sign In | Join Free | My frbiz.com
frbiz.com
Products
Search by Category
Home > Wires, Cables & Cable Assemblies >

MR484000SG1 4000W 75A High Efficiency Communication Power Module 96 Percent Efficiency Wide Input 85 300VAC Hot Swappable

Categories Telecom Power System
Brand Name: ESTEL
Model Number: MR484000SG1
Certification: ISO9001, CE, 3C, FCC, TLC
Place of Origin: China
MOQ: 1
Price: Negotiation
Payment Terms: T/T
Supply Ability: 100000
Packaging Details: carton packing
Input mode: Single-phase two-wire input
Input voltage: 85Vac to 300Vac
Nominal input: 100Vac to 120Vac 200Vac to 240Vac
Frequency range: 45Hz-66Hz
Maximum input current: ≤24A
Surge current: Meet the criteria: ETSI300132-3
Efficiency: ≥96.6%@peak value
Power factor: ≥0.99@220Vac 20-100% Load
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

MR484000SG1 4000W 75A High Efficiency Communication Power Module 96 Percent Efficiency Wide Input 85 300VAC Hot Swappable

MR484000SG1 4000W 75A High Efficiency Communication Power Module 96 Percent Efficiency Wide Input 85 300VAC Hot Swappable


1. Electrical specifications


1.1 Input characteristics


Input modeSingle-phase two-wire input
The input voltage85Vac to 300Vac
Rated input voltage110Vac / 220Vac
Nominal input100Vac to 120Vac 200Vac to 240Vac
Frequency range45Hz-66Hz
Maximum input current≤24A
The surge currentMeet the criteria: ETSI300132-3
The efficiency of≥96.6%@peak value
The power factor≥0.99@220Vac 20-100% Load
The input current is THD

<3% @≥50% Load

<8% @≥20% Load

Leakage current<3.5mA@264Vac
Rated power

Rated 4000W@176ac

(176Vac~300Vac excess output;

176Vac~85Vac linear derating to 1600W, specific as input power limit curve)

Input the insuranceL/N Wire fuse30A
Maximum input voltage320Vac(Power supply must not be damaged)
Power down retention time10ms

Note: 1. The minimum starter voltage is less than 95VAC.


1.2 Output characteristics


1.2.1 Output voltage and current adjustment rate


The output voltage+53.5Vdc
Output voltage setting value+53.5±0.1Vdc
Adjustable range of output voltage+42Vdc~+58Vdc
Unbalance degree of uniform flow≤±3%
Source effect±0.1%
Effect of load±0.5%
Accuracy of steady flow≤±0.8A
Voltage regulation accuracy±0.6%
Minimum current0A
Rated current75A
Peak current81.3A
Temperature coefficient (1/℃)≤±0.02%
Standby power consumption≤5W
Maximum capacitive load4000uF
Maximum number of parallel31

Note: The output current regulation and communication interruption of the rectifier module are as follows:

1) The output current of the rectifier module can be adjusted according to the current command. The adjustment range is 1A~81.3A.

2) If the communication between the rectifier module and the monitoring module is interrupted for more than 1 minute, the output of the rectifier module will automatically return to 53.5V and the state of

unlimited flow.


1.2.2 Output ripple and noise


Ripple and noise (peak-peak)
≤200mVp-p

Note: 1) Ripple and noise test: Ripple and noise bandwidth set at 20 MHz.


1.2.3 Output dynamic response


The voltage

overshoot

Jump slopeThe load changeRecovery time

+53.5V±5%


0.1A/uS

25%-50%

50%-75%

≤200us (±0.6%)
+58V0.1A/uS0%-100%

/( Does not trigger

overvoltage

protection )

Note: load jump cycle 4ms.


1.2.4 Output overshoot


The output voltageOvershoot voltage
bootTo turn it off
+53.5V≤1%≤1%

Note: Load range during test: minimum to maximum.


1.2.5 Startup output delay time


The output voltage220Vac@25
+53.5V3S~8S

Note: Start-up delay time is the time from AC power on to output voltage to 42VDC.


1.2.6 Power conversion


Input VoltageOutput Power
200Vac~290Vac4350W
176Vac~200VacLinear derating
176Vac4000W
85 Vac~176VacLinear derating
85Vac1600W


The output 53.5~58V is based on the upper limit power, and the output 42~53.5V is based on the external characteristics and the proportional power limit

The above is a curve that limits the maximum output power according to the input voltage; all are

theoretical limit values, and the actual limit will have a certain deviation due to the input voltage accuracy (±2V), output voltage accuracy (±0.6%) and output current accuracy (0.8A) ; The voltage error of the power conversion point is <±2V.


1.2.7 Output characteristic



Remarks: The above are the theoretical limit values, the actual limit will have a certain deviation due to the current accuracy (current error <±0.8A) .


1.2.7 Startup output delay time


The output voltage220Vac@25
+53.5V3S~8S

Note: Start-up delay time is the time from AC power on to output voltage to 42


1.2.8 Over-temperature drop curve


The

temperature

note
≤45℃With the output
45℃~75℃Linear derating
>75℃Shutdown, after shutdown since the recovery of temperature return >

Note:

The input is greater than 200Vac, the output 53.5~58V is based on the upper limit power, and the output 42~53.5V is based on the external characteristics and the ratio of the power limit;

The input is less than 200Vac, and the output 53.5~58V is limited in proportion to the input power limit; the output 42~53.5V is limited in proportion to the external characteristics and the input power limit.

The above are the theoretical limit values, and the actual limit will have a certain deviation due to ambient temperature accuracy (±2°), input voltage accuracy (±2V), output voltage accuracy (±0.6%) and output current accuracy (0.8A); The ambient temperature error of the rated point is less than ±2℃.


1.2.9 Noise voltage


Noise voltageThe maximumnote
The telephone weighs the noise voltage≤2mV
Broadband noise voltage≤50mV3.4~150KHz
≤20mV150~30000KHz
Discrete noise voltage≤5mV3.4~150KHz
≤3mV150~200KHz
≤2mV200~500KHz
≤1mV500~30000KHz

1.3 Protection function


1.3.1 Output short circuit protection


output voltageNote
+53.5VLong - term short circuit, can be automatically restored after short circuit disappeared

1.3.2 Output overvoltage protection


Over voltage protection can be divided into internal and external overvoltage protection. The internal overvoltage fault range is 58.5VDC~ 60.5VDC, which can be set by monitoring. In case of failure, the module locks. If the external voltage is greater than 63VDC and lasts more than 500ms, the module is locked. After entering the lock machine protection state, it is necessary to disconnect the AC power first, and then power on again, so that the power can work again.


1.3.3 Output undervoltage warning


The range is 37VDC~39VDC. When it is lower than the undervoltage alarm value, it will output normally and report an alarm..


1.3.4 Input overvoltage protection


The input voltagenote
310±10VacOutput off, voltage can be recovered after normal
Recovery point return >10V

Note: Input overvoltage protection shall be tested at 75A rated load.


1.3.5 Input undervoltage protection


The input voltageNote
80±5VacOutput off, voltage can be recovered after normal
80Vac-95VacOutput recovery, output recovery point return >;5V

1.3.6 Over temperature protection


TemperatureNote
≤45℃The module can output the maximum output power without over-temperature protection, and the module operates normally
45℃~75℃The module power is linearly derated to 2000W
>75℃Shutdown, self-recovery temperature difference after shutdown>10℃

1.4 Communication function between rectifier module and monitoring module


The CAN bus communication mode is adopted between the rectifier module and the monitoring module, which supports the remote software version upgrade, and the module's address CAN be set through the

address board.

After the communication between the rectifier module and the monitoring is interrupted for 1 minute, the rectifier module starts up and the output voltage and current limit values return to the default values.

The CAN interface in the rectifier module needs to be designed in isolation. The power supply of CAN is + 5VDC, which is provided inside the rectifier module.

The main monitoring information of rectifier module is as follows:

1) Voltage regulation and current regulation function: to meet the floating charging requirements of the battery and to meet the voltage regulation requirements;

2) Single module switch machine control;

3) Protection and alarm information feedback:


Utility fault: Utility fault (AC input over voltage);

Module protection: temperature warning;

Module failure: no output caused by over-voltage shutdown, fan failure, over-temperature shutdown or other internal reasons of the module;

(The module is in hibernation and shutdown state, and the mains power failure is not reported to the module fault).


1.5 LED


The power supply LED indicator is installed on the side of the power panel. The output state is shown in the table below.

mandatory signIndicator lightnormalabnorma lAbnormal reason
Power running indicatorcolorstatestatePower failure (no AC input, AC input over voltage), module no output.
Warning lightgreenbrightdestroyTemperature warning (the ambient temperature exceeds 65 ℃ ~ over temperature shutdown). Dormancy shutdown (the module only lights the alarm indicator light, the module does not report the alarm). Communication interruption (warning light flashing) . Input overvoltage warning, (input voltage over 290VAC ~ overvoltage protection).
Failure lighthuangdestroybrightInput overvoltage, input undervoltage, output overvoltage, bus overvoltage, bus undervoltage, fan failure, environmental overtemperature, input voltage type error, environmental temperature sampling NTC abnormity, input ultra-high voltage.

2. Insulation performance


2.1 Insulation Impedance


input-to-output

Test voltage 500VDC, insulation resistance ≥2M

(Normal atmospheric pressure, room temperature, relative humidity < 90%, no condensation)

Input to the protected area
Output to the protected area

2.2 Resistant to high voltage


input-to-outputDC voltage 4240VDC1minute ≤1mA

Input to the

protected area

DC voltage 2120VDC 1minute ≤1mA

Output to the

protected area

Equivalent DC voltage 710VDC 1minute ≤1mA

Note: if the circuit has lightning protection device, the voltage test should be performed after the opening of the electrical gap tube, the input lines should be short connected (L&N) together, and all the output lines should be short connected together.


3. Safety standards


Power supply safety meets the following standards:

GB4943

IEC/EN60950 IEC/EN62368-1

Power supply safety certification:

CE certification (LVD and EMC directive requirements)


Quality MR484000SG1 4000W 75A High Efficiency Communication Power Module 96 Percent Efficiency Wide Input 85 300VAC Hot Swappable for sale
Send your message to this supplier
 
*From:
*To: Tianjin Estel Electronic Science and Technology Co.,Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0