Sign In | Join Free | My frbiz.com |
|
Categories | Digital I O Module |
---|---|
Brand Name: | GE |
Model Number: | IC200MDL636 |
Place of Origin: | USA |
Price: | negotiation |
Payment Terms: | T/T |
Supply Ability: | 1 |
Delivery Time: | 5-8 work daysRockwell Automation |
Packaging Details: | New in original boxRockwell Automation |
Condition: | new |
Nominal output voltage: | 120 / 240 VAC |
Product Type: | Output Module |
warranty: | 1 year |
Output current per point: | 2A |
Rated Voltage: | 120/240 V AC |
Output Voltage Range: | 85/264 V AC |
Inrush current: | 25 A for one cycle |
Company Info. |
Wisdomlong Technology CO.,LTD |
View Contact Details |
Product List |
GE IC200MDL636 provide four groups of 8 discrete inputs c input
on/off response time is 0.5ms
Product information GE IC200MDL636:
IC200MDL636 is a 48 VDC Positive Negative Logic Input Module with
32 Points manufactured by GE Fanuc for the VersaMax series. The
IC200MDL636 provides four sets of eight discrete inputs.
Inputs in each set can be either positive logic inputs or negative
logic inputs. Positive input logics receive current from input
devices and return the current on the common while negative-logic
inputs receive the same current from the common and return current
to the input device. Input devices are linked between the input
terminals and common terminals. The number of points that can be on
at the same time is based on factors, including external voltage,
orientation of the module and DIN rail, and ambient temperature.
The IC200MDL636 is powered by the backplane. Intelligent processes are performed by the CPU or NIU. The module provides 32 bits of discrete input data. The IC200MDL636 module has individual green LEDs that indicate the on/off state of each input point. Backplane power must be available for LEDs to perform. The green OK LED will display ON when backplane power is recognized.
The basic input on/off response time of the IC200MDL636 module is
0.5ms. Some applications may, however, need additional filtering to
handle noise spikes or switch bounce situations.
The module’s basic input on/off response time is 0.5ms. For some
applications, it may be preferable to add additional filtering to
compensate for conditions such as noise spikes or switch bounce.
Input filter times of 0ms, 1.0ms, or 7.0ms are selectable via
software configuration, for total response times of 0.5ms, 1.5ms,
and 7.5ms respectively. The default is 1.0ms filter time (total
response time is 1.5ms)
In the Features:
• EQUIPMENT LABELED WITH REFERENCE TO CLASS I, GROUPS A, B, C & D,
DIV. 2 HAZARDOUS LOCATIONS IS SUITABLE FOR USE IN CLASS I, DIVISION
2, GROUPS A, B, C, D OR NON-HAZARDOUS LOCATIONS ONLY
• WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY
IMPAIR SUITABILITY FOR CLASS I, DIVISION 2;
• WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS LOCATIONS, TURN
OFF POWER BEFORE REPLACING OR WIRING MODULES; AND
• WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS
POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE
NONHAZARDOUS.