Product Name: PH ORP controller
PH Range: 0 ~ 14pH
ORP Range: ± 2000mV
Temperature Range: -10~150℃ /14~302℉
Resolution: 0.01pH/1mV/0.1℃
Protection Grade: IP66
Operating Temperature: 0~60℃
Power Supply: 18 ~ 36V DC
Shell Material: Enhanced ABS
Power Consumption: 3W
Mounting Method: Panel installation
Weight: 500g
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

RS485 Online pH ORP Meter Controller With Data Recording Function For Water


High Quality RS485 Online pH ORP Meter Controller with Data Recording Function For water


‍pH/ORP controller (also known as pH meter) equipment is suitable for the control of PH and ORP values in electroplating, metallurgy, textile, chemical and other wastewater, giving new life to the traditional chemical treatment method, fully realizing automatic monitoring, automatic medication, to ensure that the discharge of wastewater to meet the national discharge standards. It can not only reduce the labor intensity of operation, but also greatly save the consumption of chemical raw materials, with obvious environmental and economic benefits. This kind of equipment with the company's production of air float or settling tower solid liquid separation equipment can form a complete industrial (electroplating) wastewater treatment system.


Advantages of pH/ORP controller:

  • pH glass electrode measurement method
  • Two configurable SPST multifunction relays
  • With 1 high-precision 0/4-20mA current output
  • 3.2 inch LCD screen, rich content
  • Support multiple installation methods
  • AC and DC power modes, both wide voltage
  • Housing material reinforced ABS, protection class IP66


pH ORP controller Parameters:

Display RangepH: 0~14pH
ORP: -2000mV~2000mV
Temp.:-10~+150℃
ResolutionpH: 0.01pH ORP: 1mV Temp.: 0.1℃
Accuracy±0.02pH/±2mV
Temp. CompensationNTC10K/PT1000 automatic or manual
Relay ControlChannel Quantity: 2
Control Type: main value control/temp. control/wash control
Contact Type: SPST
Contact Capacity: 3A 250V AC
Current OutputChannel Quantity: 1
Output Type: active 4~20mA or 0~20mA
Max. Load: 1000Ω
Display Screen3.2 inch graphic LCD display
Configuration informationPower failure protection, parameters are retained indefinitely
Operating Environment0~+60℃, relative humidity 0~95%, no condensation
Storage Environment-20~+70℃, relative humidity 0~55%, no condensation
Power Supply100~240VAC or 18~36VDC, 3W Max
Installation MethodPanel / wall / pipe mounting
Instrument Dimension144*144*120 (unit: mm)
Protection GradeIP66
Instrument WeightAbout 800g


Wiring instructions for PH ORP Controller:


Place the controller with the screen facing down on the foam pad.Use a phillips screwdriver to unscrew the screws of the back cover.Take out the cable glands.Insert the cable glands into the reserved hole,tighten the nut inside the rear cover.Loosen the nut on the outside of the rear cover.Insert the power cable into the gland on one side.Pass the pH sensor wire through the other side.Note: Do not cross the power line and the sensor line to prevent the drift of the measurement data caused by interference.The power cable has two ends.The brown live wire is connected to the terminal hole marked "L".The blue neutral wire is connected to the terminal hole marked "N".The pH sensor with temperature has four wire ends and are usually marked with a wire mark.The red wire end is connected to the terminal hole marked "ACT".The black wire end is connected to the terminal hole marked "REF".Two temperature wire ends are connected to the terminal hole marked "TEMP" .Both the left and right sides of the ACT terminals can be inserted, and they should be tightened after insertion.The pH sensor without a temperature unit has two wire ends.Just insert it according to the line mark .After the wiring is completed, close the back cover, tighten the screws on the four corners, and tighten the nuts of the glan head.Turn on the power switch,The pH controller screen will light up.Now it can start to work normally.


pH ORP controller Applications:

Water treatment monitoring: drinking water, surface water source water quality, groundwater, environmental sewage discharge monitoring, urban drainage network monitoring
Industrial process monitoring: chemical industry, petroleum, paper making, food and medicine, PCB electroplating, etc


If you are interested in more product information about pH ORP controller APX2-C1, please contact us.




Quality RS485 Online pH ORP Meter Controller With Data Recording Function For Water for sale
Send your message to this supplier
 
*From:
*To: Suzhou Delfino Environmental Technology Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0