Model: | 3AV5-12 |
Breaking Capacity: | 20, 25, 31.5, 40KA |
Rated Voltage: | 12KV |
Rated Current: | 630A, 1000A, 1250A, 1600A, 2000A, 2500A, 3150A |
Mechanical Life: | 20000 times |
Motor Voltage: | DC/AC 110V 220V |
Types: | withdrawable, stationary, side-mounted |
Warranty: | 1 year |
Company Info. |
METALWORK MACHINERY (WUXI) CO.LTD |
Verified Supplier |
View Contact Details |
Product List |
3AV5 circuit breaker series is indoor high-voltage switchgear, suitable for rated voltage 12 kV, frequency 50 Hz three-phase power system, as protection and control appliances, with high reliability, easy operation, simple maintenance and other characteristics. The circuit breaker can be used for middle-type switchgear and fixed switchgear as well as oil-free transformation. Because of the special advantages of vacuum circuit breaker, it is especially suitable for frequent operation requiring rated current, or many times to break the short-circuit current. The 3AV5 vacuum circuit breaker has three installation modes: fixed type, extraction type and side mounted. For special requirements, please contact the manufacturer.
Technical Parameters:
Items | Unit | Date | |||
Rated voltage | KV | 12 | |||
Rated impulse withstand voltage | 75 | ||||
Rated short-time power frequency withstand voltage (1min) | 42 | ||||
Rated frequency | Hz | 50~60 | |||
Rated short-circuit breaking current | KA | 20 | 25 | 31.5 | 40 |
Rated current | A | 630 1000 1250 | 630 1000 1250 1600 | 1250 1600 2000 2500 | 1600 2000 2500 3150 4000 |
Rated short-time withstand current | KA | 20 | 25 | 31.5 | 40 |
Rated peak tolerable current | 50 | 63 | 80 | 100 | |
Rated short-circuit making current (peak value) | 50 | 63 | 80 | 100 | |
Secondary circuit power frequency withstand voltage (1min) | V | 2000 | |||
Rated operation sequence | O-0.3S-CO-180S-CO O-180S-CO-180S-CO (at 40KA) | ||||
Rated single/back-to-back capacitance bank breaking current Set breaking current | A | 630/400 (40KA 800/400) | |||
Rated short-circuit breaking current DC flow percentage | ≤35% | ||||
Opening time (rated voltage) | ms | 20-50 | |||
Closing time (rated voltage) | ms | 30-70 | |||
Mechanical life | times | 20000 | |||
Rated short-circuit breaking current breaking times | times | 50 (40KA 30) | |||
Allowable wear accumulate thickness of moving and static contacts | mm | 3 | |||
Rated closing operating voltage | v | AC110/220 DC110/220 | |||
Rated opening operating voltage | v | AC110/220 DC110/220 | |||
Rated voltage of energy storage motor | v | AC110/220 DC110/220 | |||
Rated power of energy storage motor | w | 80 | |||
Contact opening distance | mm | 11±1 | |||
Contact stroke | mm | 3.5±1 | |||
Contact bounce time | ms | ≤2 (40KA ≤3) | |||
Three - phase opening and closing heterogeneity | ms | ≤2 | |||
Average closing speed *1 | m/s | 0.9-1.3 | |||
Average closing speed*2 | m/s | 0.4-0.8 | |||
Main circuit resistance | μΩ | ≤50 (630A) ≤45 (1250A) ≤35 (1600-2000A) ≤25 (above 2500A) |
![]() |