Sign In | Join Free | My frbiz.com |
|
Categories | High Voltage Tester |
---|---|
Brand Name: | United electrical |
Model Number: | ZGF |
Certification: | ISO9001, ISO14001, OHSAS18001 |
Place of Origin: | Wuhan, China |
MOQ: | 1pcs |
Price: | negotiable |
Delivery Time: | 7 working days |
Packaging Details: | 1 pcs / wooden box with wrapping film |
Specification: | 60/2,120/2,200/2,300/5 |
Output Voltage (kV): | 60,120,200,300 |
Output Current (mA): | 2,2,2,5 |
Output power (W): | 120,240,400,1500 |
Charging Current (mA): | 3,3,5,5 |
Controll Case Weight(kg): | 10.1,13,13.1,13.1 |
Voltage Measurement Error: | ±1% |
Current Measurement Error: | ±0.5% |
High Precision Portable Cable Hvdc Dc Hipot 5mA 400kv DC High Voltage Tester
Product Introduction :
DC high voltage generator is mainly used in the electric power
department, power department of industrial and mining, metallurgy,
iron and steel enterprise for zinc oxide lightning arrester, power
cables, transformers, circuit breakers, generators and other high
voltage electrical equipment of DC withstand voltage test or DC
leakage current test.
Product Features:
1. the case is portable and convenient to carry.
2. Using AIPWM technology, adjusts the PWM inaccuracy linearity
make the accuracy is greatly improved. The ripple coefficient is
less than 1%.
3. AI zinc oxide arrester and oil immersed transformer measuring
function can directly save experiment report, and the accuracy is
less than 1%. Keep manual 0.75 UDC1mA.
4. Used the AI technology screen setting over-voltage protection
and over-current protection to replace the digital dial switch only
can set voltage value, cannot set current value and voltage drift
problem. Error of 1% or less.
5. The full measuring range smoothly adjust pressure, voltage
regulation accuracy is less than 1%, stability is less than 1%, the
voltage current error is less than 0.5%±1 letter.
6. with total time T1 and segmented time T2, and any voltage,
current chronograph function.
7. The instrument added the calendar and time function.
Main Parameters:
Specification Technology parameter | 60/2 | 120/2 | 200/2 | 300/5 |
Output Voltage (kV) | 60 | 120 | 200 | 300 |
Output Current (mA) | 2 | 2 | 2 | 5 |
Output power (W) | 120 | 240 | 400 | 1500 |
Charging Current (mA) | 3 | 3 | 5 | 5 |
Controll Case Weight(kg) | 10.1 | 13 | 13.1 | 13.1 |
Double voltage cylinder weight(kg) | 2.3 | 3.2 | 8.0 | 10 |
Double voltage cylinder specification(mm) | Ф90 340 | Ф90 470 | Ф110 910 | Ф110 1200 |
Voltage Measurement Error | ±1% | |||
Current Measurement Error | ±0.5% | |||
Over-voltage Setting Error | AI technique setting over-voltage and over-current protection. Error ≤±1% | |||
0.75 Switch Error | 0.75UDC-1mA high precision single touch button(accurancy≤±1%)is much suitable for zinc oxide arrester test. | |||
Ripper Coefficient | ≤±1% | |||
Working Method | Intermittent use: rated load for 30 minutes 1.1 times rated voltage use: 10 minutes | |||
Working Environment | Temperature:-10ºC~+40ºC | |||
Relatived Humidity:When the room temperature is 25 ºC is not greater than 85% (no lon) | ||||
Altitude: below 1500 meters | ||||
Capacitive Load | Tested product capacity no restriction | |||
Structure Features | Electrical insulation double voltage cylinder | |||
Air insulation, no leakage |
Quality Guarantee: One year quality guarantee after shipment.
![]() |