Residential Vfd Pump Drive , Water Supply Pump Inverter Drive Energy Saving

Categories Variable Frequency Drive Pump Control
Place of Origin: China
Brand Name: Kinda
Model Number: KD386
MOQ: Negotiable
Price: Negotiable
Delivery Time: 3~8 Day
Payment Terms: TT
Supply Ability: Adequate inventory
control: Main/slave control energy saving
installation: Simple wiring installation
PCB protection: Spray three anti-paint to protect the circuit board intelligently and efficiently
design: Modular design, compact structure, easy maintenance and enhanced product interchangeability
start up: Simple parameter setting, one-button start automatic addition and subtraction pump control
run: Smooth main/slave switching, no change in water pressure
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Residential Vfd Pump Drive , Water Supply Pump Inverter Drive Energy Saving

Residential Area Variable Frequency Drive Pump Control Water supply


When the water supply automatic control system is working, when the water consumption is changed by the high sensitivity pressure sensor installed on the water supply pipe network, the device detects the pressure change of the water supply pipe network. When the pressure of the pressure transmitter is the largest, the frequency of the inverter is the lowest, the minimum speed of the pump motor. When the pressure of the pressure transmitter is the smallest, the frequency of the inverter is the highest, the speed of the pump motor is the highest, and the frequency of the inverter changes with the water consumption. And change.


After the microcomputer judges the calculation and compares it to the set pressure, it sends a command to change the frequency to the controller. By changing the frequency, the controller automatically adjusts the peak and valley water consumption to ensure that the water supply network pressure is constant, changing the speed of the pump motor and the number of pumps activated.
Constant pressure water supply inverters are widely used in residential, hotel, agricultural constant water pressure stabilization products.



Function codeDefault valueSet valueDescription
F1-111I# inverter11# inverter (master), it must connect the pressure sensor.
2# inverter22# inverter (slave / standby master), connect the pressure senor.
3# inverter33# and 4# inverters (slave).
4# inverter4Warning: the address of each inverter cannot be the same, otherwise, the system will work abnormally.
F0-0012Multiple pumps system
F0-010.4MPaCustomer set1. Please set it correctly based on requested pressure, the unit is MPa, 1MPa=10bar.
2. Most of the family used systems, the pressure is 0.3~0.4MPa (3~4bar)
F0-0280%Customer setWake up pressure; it is the percentage of F0-01.
F0-0300It must be set as “0” while use 0~10V remote pressure gauge.
1It must be set as “1” while use 4~20mA pressure transducer.
F0-041.6MPa1.6MPa1. To set the maximum measure range of pressure transducer.
2. It must be set correctly, otherwise it may cause pressure is inaccurate.
F0-25300MinCustomer setTo set the running time as master pump, when time arrive, it switches to next pump as master.
When set F0-25=0, this pump will only work as slave pump.