Sign In | Join Free | My frbiz.com
frbiz.com
Products
Search by Category
Home > Electrical Wires >

BS6387 Mineral Insulated Cable Plain Copper Sheath Low Voltage Fire Resistant

Categories Mineral Insulated Cable
Name: Mineral Insulated Cable
Insulation: Magnesium Oxide
Sheath: Plain copper
Voltage Rating: 300/500V and 450/750V
Temperature Rating: -10°C to 250°C
Sheath Colour: Plain copper
Place of Origin: Guangzhou, China
Brand Name: SUNWIN
Certification: ISO9001, ISO14001, OHSAS18001
MOQ: Negotiable
Price: Negotiable
Packaging Details: 100 m / tied, or customized
Delivery Time: 10 day
Payment Terms: 30% deposit, the balance is settled on the delivery date
Supply Ability: 100,000 m / month
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

BS6387 Mineral Insulated Cable Plain Copper Sheath Low Voltage Fire Resistant

BS6387 Mineral Insulated Cable Plain Copper Sheath Low Voltage Fire Resistant


Click to view our full range of BS6387 standard cables


British Standard BS6387 covers the performance requirements and test methods for cables required to maintain circuit integrity under fire conditions, It has been developed to assist installation designers with their assessment of the fire performance characteristics of various types of cables and their selection for specific applications. In particular, it covers the cables' ability to maintain circuit integrity against set time and temperature parameters.

BS6387 covers fire resistant cables with a voltage rating of 300/500V and 450/750V. It also covers mineral-insulated cables manufactured in accordance with BS6207.

BS6387 Cable categories


Resistance to fire alone

Category A

650oC for 3 hours

Category B

750oC for 3 hours

Category C

950oC for 3 hours

Category D

950oC for 20 minutes (short duration)



Resistance to fire with water (W)

Category X

650oC for 3 hours

Category Y

750oC for 3 hours

Category Z

950oC for 3 hours


For example, a cable meeting the requirements in terms of their ability to maintain circuit integrity for 3 hours at 950oC and also for 3 hours at 650oC when exposed to fire and water would be referred to as CWX.

Other tests covered under BS6387 include voltage tests on completed cables, tests for bending characteristics, tests for resistance to impact at ambient temperature, and tests for fire resistance characteristics.

Eland Cables is a leading supplier of cables designed to maintain circuit integrity under fire conditions, inclu

ding our Firetec cables and a comprehensive range of mineral insulated copper cable manufactured in accordance with BS6387.


CONDUCTORS


NOMINAL CROSS SECTIONAL AREA

mm²

MAXIMUM RESISTANCE OF CONDUCTOR AT 20ºC

ohms/km

118.1
1.512.1
2.57.41
44.61

ELECTRICAL CHARACTERISTICS

Current Carrying Capacity


NO. OF CORES

NOMINAL CROSS SECTIONAL AREA

mm²

SINGLE PHASE AC OR DC

Amps

THREE PHASE AC

Amps

2117-
21.521-
22.528-
2436-
31-14
31.5-17
32.5-23
41-14
41.5-17
42.5-23
71.512-
72.516-

Voltage Drop


NO. OF CORES

NOMINAL CROSS SECTIONAL AREA

mm²

SINGLE PHASE AC OR DC

mV/A/M

THREE PHASE AC

mV/A/M

2142-
21.528-
22.517-
2410-
31-36
31.5-24
32.5-14
41-36
41.5-24
42.5-14
71.528-
72.517-

* Method of cable support should withstand a similar temperature and donation to that of the cable.

Product Tags:

micc cable

  

mineral insulated wire

  
Quality BS6387 Mineral Insulated Cable Plain Copper Sheath Low Voltage Fire Resistant for sale
Send your message to this supplier
 
*From:
*To: Guangdong Shengyu Cable Industry Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0