Sign In | Join Free | My frbiz.com
frbiz.com
Products
Search by Category
Home > Fuses >

1000VDC High Speed Fuses , Semiconductor Energy Storage System Fuses

Categories Energy Storage System Fuse
Brand Name: Dissmann
Model Number: MEV-J-G70
Certification: UL,TUV
Place of Origin: China
MOQ: 100pcs
Price: Negotiable
Payment Terms: T/T, L/C
Supply Ability: 1,000,000pcs
Delivery Time: 5-8days
Packaging Details: Standard Carton Packing
Material: Ceramic
Colour: White
Usage: Energy Storage systems,Photovoltaic,Solar inverter
Rated Voltage: 1000VDC
Current Rating: 700A
Keyword: Energy Storage Systems Fuses
Standard: IEC60269-4, UL248-13
Breaking Capacity: DC50KA
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

1000VDC High Speed Fuses , Semiconductor Energy Storage System Fuses

DC50KA High Breaking Capacity Energy Storage Systems Fuses


1.Basic Information:

Rated Voltage:1000VDC or lower

Rated Current:700A

Breaking Capacity:DC50KA

Class of protection:aR

Related Standards:IEC60269-4, UL248-13,EU and RoHS directives


2.Product Characteristics:

ModelRated Current (A)I²t(A²Sec)Power Loss (W)Installation
Pre-ArcAfter1.0In
MEV-J-G70700A180,0001,082,00075.6Bolt Install M12,
Recommend Torque: 28±11N.m

3.Product Application:

This series of products are square tube bolt fuse, low I²t, Strong current limiting capacity, high breaking capacity and other characteristics, suitable for rail transit, electric vehicles, ships and other industrial applications. It can be used as short circuit overcurrent and backup protection for energy storage system, power system, wire and other devices and equipment.


Note: All test data in this specification are measured in standard environment, test parameters and wiring according to IEC60269.


4.Product Dimension:


5.Installation conditions

Normal working conditions

The fuses are installed separately in unventilated natural air, in addition to connecting wires, no other heat generating parts or heat dissipating parts within 1m.


The fuse connection terminals should ensure stable and reliable electrical contact; contact resistance should not significantly affect fuse operation.


The fuse can be installed vertically, horizontally or obliquely. If relying on spring pressure to ensure electrical connection fuse, when installing, a suitable location should be selected to avoid the adverse effects of gravity and vibration on the electrical connection.


Test equipment
Production equipment
Our Certificates
Quality 1000VDC High Speed Fuses , Semiconductor Energy Storage System Fuses for sale
Send your message to this supplier
 
*From:
*To: Dissmann | Global Expert Fuse for EV | HEV | Photovoltaic | Battery | Energy Storage Solutions
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0