Sign In | Join Free | My frbiz.com |
|
Categories | Vacuum Circuit Breaker |
---|---|
Brand Name: | XG |
Model Number: | ZW32 |
Certification: | ISO, type report |
Place of Origin: | XIAN, China |
MOQ: | 1 SET |
Payment Terms: | L/C, T/T, D/A, D/P, Western Union, MoneyGram |
Supply Ability: | 2000 SET |
Delivery Time: | 3-7 DAYS |
Packaging Details: | exporting package |
Application: | Outdoor |
Rated Voltage: | 11KV 24KV 22KV |
Rated Current: | 400A 630A, 1250A, 1600A, 2000A, 2500A, 3150A, |
Rated Frequency: | 50/60Hz |
Poles No.: | 3 |
Phase: | 3 |
Medium: | vacuum |
Usage: | pol mounted |
Company Info. |
Xi'an Xigao Electricenergy Group Co., Ltd. |
Verified Supplier |
View Contact Details |
Product List |
1. Electric Operation Auto Recloser 33kv Outdoor Vacuum Circuit Breaker
ZW32-12 Series Outdoor High Voltage Vacuum Circuit Breaker is widely used in the power system of three-phase, which has AC 50Hz and 10~12Kv voltage level. The main function of the equipment is breaking and closing the loading current, and also it can protect electric consumption by tele-control and tele-monitor. Meanwhile, ZW32-12 can be used in both of Business biased and household biased.
2. Advantages:
2.1. It conforms to the national GB1984“High voltage alternating current circuit breaker”.
2.2 It conforms to professional standard JB3855“3.6~40.5 kV voltage vacuum circuit breaker outdoor exchange” and relevant IEC standard.
3. Condition:
Ambient temperature:-40°C~+40°C
Wind pressure:≤700Pa(equivalent to wind speed 34m/s)
Relative humidity:≤95%or≤90%
Altitude:≤2000m
Seismic intensity:≤8
*No fire, explosion, serious filthy, chemical corrosion and violent vibration of places.
4. Main technical parameters:
Item | Unit | Parameter | ||||
Rated Voltage | KV | 12 | ||||
Rated Insulation Level | 1 Min power frequency witstand Voltage | Dry test | 42 | |||
Wet Test | 34 | |||||
Lighting impulse withstand voltage(peak) | 75 | |||||
Rated Current | A | 630 | 400 | 200 | ||
Rated short-circuit breaking current | KA | 20 | 16 | 12.5 | ||
Rated opertaing sequence | O-0.3s-CO-180s-CO | |||||
Rated short-circuit breaking current time | Times | 30 | ||||
Rated short-circuit closed current(peak) | KA | 50 | ||||
Rated peak withstand current | 50 | |||||
Rated short-time withstand current | 20 | |||||
Rated short-circuit duration | s | 4 | ||||
opening time (magnetic releasing) | Max operating voltage | ms | 23~45 | |||
Rated operating voltage | 23~60 | |||||
Min operating voltage | 25~45 | |||||
close time | ms | ≤100 | ||||
total break time | ≤20 | |||||
Mechanism life | Times | 1000 | ||||
rated input power of Storage energy motor | Times | 40 |