600W Low Frequency Transformed Based
off Grid Backup Inverter Charger
Energier Essential bi-directional inverter can be used in multiple
applications.You can use it
to compose power backup system. Or, with a quick setting,you can
compose a simple solar
hybrid system either with grid or diesel-generators.
Under SOLAR mode, you can use Energier essential Inverter charger
combination to compose a
solar hybrid system, of which solar energy will be used as priority
and will bring grid/D.G. in and
meantime charge battery upon battery runs to protection level
With AC input available from the grid or generator, power is pass
through Energier essential Inverter
charger combination to operate connected AC load and being covered
to DC to charger the battery at
the meantime. If AC input power failed or fall out of specification
and is no longer qualified as good AC,
a quick transfer take place and Energier essential Inverter charger
combination start converting DC
power from battery into AC power to supply connected AC load.
Features,
-Equalization charging program was available
-Compatible with majority of cheap generators in the market
-Designed to work with weak grid
-Bi directional inverter with pure sine wave output
-Can be applied for power backup and solar hybrid system
-Designed for tropical region with working temperature up to 60℃
-Optional CM was available for automatic generator start
-Dry contacts
-Optional SNMP card for remote internet access
-High performance designed for all kinds of home appliances
-TBB premium II multi stage charging algorithm with built in
-automatic temperature compensation
Picture

Specification
Model No. | 12Vdc | CS0625L | CS1040L | CS2080L | | |
| 24Vdc | CS0615M | CS1020M | CS2040M | CS3060M | CS4080M |
| 48Vdc | | | | CS3030S | CS4040S |
INVERTER |
Nominal Voltage | 12Vdc, 24Vdc, 48Vdc |
power 30mins @25℃ (W) | 600 | 1000 | 2000 | 3000 | 4000 |
Cont.power@25℃ (W) | 600 | 1000 | 1800 | 2500 | 3600 |
Cont.power@40℃ (W) | 600 | 1000 | 1500 | 2000 | 3000 |
Cos φ | 0.9-1 |
Surge | 300% |
Output voltage【1】 | 230VAC or 110VAC ± 2% | 230VAC ± 2% |
Output frequency | 50Hz or 60Hz ± 0.1% |
Efficiency (MAX.) | 12Vdc | 88% |
| 24Vdc | 88% |
| 48Vdc | 92% |
Bypass range | UPS mode | 184VAC-264VAC/92VAC-132VAC | 184VAC-264VAC |
| GEN mode | 160VAC-280VAC/80VAC-140VAC | 160VAC-280VAC |
Crest factor | 3:1 |
THD | <3% |
Zero load power | 17 | 22 | 27 | 36 | 62 |
Zero load power (power save mode) | 4 | 5 | 7 | 9 | 15 |
Output circuit breaker | 5A | 10A | 15A | 30A | 30A |
Overheat protection | auto disconnect |
Overload protection | auto disconnect |
shortcut protection | auto disconnect |
Charger |
Nominal Output Voltage | 12Vdc, 24Vdc, 48Vdc |
Max Output current (A) - adjustable | 25/15 | 40/20 | 80/40 | 60/30 | 80/40 |
AC Input range | UPS mode | 184VAC - 264VAC/92VAC-132VAC | 184VAC - 264VAC |
| GEN mode | 160VAC - 280VAC/80VAC-140VAC | 160VAC - 280VAC |
Battery types | AGM / GEL / LFP / Flooded |
Absorption time | variable |
Temperature compensation | -4mV/℃/cell |
Charger circuit breaker | 5A | 10A | 15A | 30A | 30A |
Other Data |
Transfer time | UPS mode | 15ms |
| GEN mode | 2s |
Transfer switch | 40A |
Battery connector | M8 x 2 |
AC connector | Terminal block (M3 screw) |
Mechanical Data |
Enclosure | Steel with powder paint |
Dimension (mm) | 444x186x135 | 512x216x176 |
Net Weight (kgs) | 9.5 | 14 | 16 | 18.5 | 22.5 |
Cooling | Forced fan |
Protection | IP20 |
Standard |
Safety | EN60950-1 |
EMC | EN55022,EN55024 |
【1】Output voltage: 220VAC/60Hz for Philippines |