Sign In | Join Free | My frbiz.com |
|
Categories | MV Voltage Transformer |
---|---|
Brand Name: | Shenzhen Chuangyin Co., Lt |
Model Number: | JDZW1-12R |
Certification: | KEMA/type test report |
Place of Origin: | China |
MOQ: | 1pc |
Price: | Negetiable |
Payment Terms: | L/C, T/T |
Supply Ability: | 80000.00pcs per year |
Delivery Time: | 8days |
Packaging Details: | Polywood |
Insulation Type: | Dry /Silicone composite insulation |
Voltage: | 12kV 24kv 36kv |
Application: | Outdoor indoor |
Properties: | Single fase |
Applied standard: | IEC 61869-1 &3 (IEC 60044-2) |
Rated insulation level: | 12/28/75kV |
Color: | Brown Red |
Material: | Epoxy resin cast |
burden: | 0.8 Cos factor |
frequency: | 50/60HZ |
Company Info. |
Shenzhen Chuangyin Co., Ltd. |
Verified Supplier |
View Contact Details |
Product List |
Chuangyin Voltage Transformer-JDZW1-12R
Description:
This product is fully enclosed outdoor single-phase voltage transformer, epoxy resin and silicone rubber composite insulation support type. The outer sheath and sheds are made of high temperature vulcanized silicone rubber, good hydrophobicity, and highly improved the contamination flashover voltage. It has anti-aging property and with tracking resistance.
VT has inserted MV fuse in the primary terminal, with protective rubber cap for animal protection and sealing function. The transformer is suitable for rated frequency of 50/60Hz, the highest equipment voltage 12kV system. Mainly for measuring, energy metering, protection and auxiliary power supply, etc.
Basic technical data:
1. Installation: Outdoor
2. Insulation type: Dry, Silicone composite insulation
3. Highest voltage for equipment Um (r.m.s.) 12kV
4. Rated power-frequency withstand voltage (r.m.s.): 28kV
5. Rated lightning impulse withstand voltage (peak): 75kV
6. Rated frequency: 50Hz / 60Hz
7. Applied standard: IEC 61869-1 &3 (IEC 60044-2)
Specification:
Rated Primary Voltage (kV) | Rated Secondary Voltage (V) | Accuracy classes combination | Rated Burden (VA) | Thermal limiting Output (VA) | Rated Insulation Level (kV) | |
10 11 | 100 110 115 120 | 220 240 | 0.2 | 15 | 500 | 12/28/75 |
0.5 | 50 | |||||
0.5/3 | 30/300 |
![]() |