Sign In | Join Free | My frbiz.com
frbiz.com
Products
Search by Category
Home > Air Conditioners >

62 DBA Noise Level Heat Pump Heating And Cooling AC ASHP Units With Two Fans

Categories Heat Pump Heating And Cooling System
Brand Name: Yushen
Model Number: SLNC-075Y
Certification: CCC, ISO, CQC
Place of Origin: China
MOQ: 1 set
Price: negotiable
Payment Terms: T/T
Supply Ability: 10 sets/day
Delivery Time: 1-2 weeks
Packaging Details: Reinforced Carton box with wooden tray
Key word: low temeprature AC ASHP units
Compressor capacity: 25HP
Function: Heating and cooling
Fans: two
working conditions: -25C ~+45C
noise level: 62DBA
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

62 DBA Noise Level Heat Pump Heating And Cooling AC ASHP Units With Two Fans

Ultra Low Temperature Heating and Cooling Heat Pump Air Source for Office Building


Brief Introduction

1. The effect of low temperature heating is not attenuated
The ultra-low temperature frequency conversion air-enhanced compressor is used to achieve stable operation at -25 °C, and the heating stability at -20 °C is not attenuated.
2. Continuous heating is better than air conditioning in low temperature environment
When the air conditioner is below 0 °C, the heating effect is greatly reduced, which leads to the fact that some areas are “cold and cold, and the air conditioner cannot be used normally”. The ultra-low temperature air source heat pump hot air enthalpy can continuously and stably heat at -25 ° C low temperature environment, and the application range is wider, and the use process is more worry-free.
3. One machine is more economical than air conditioner
Refrigeration is the duty, heating is the ability, one machine to solve the two needs of winter heating, summer cooling. Compared with the use of air conditioning or other refrigeration and heating methods, it is convenient and can greatly reduce the user's use cost.
4. Floor heating heating experience is more comfortable than air conditioning


Technical data


ModelSLNC-075Ycode name.pdf
Compressor capacity25HP
FunctionHeating and Cooling
Electricity380V-3N-50Hz
Working conditions-25~+45
DataHeataNominal capacityKW44.5
Input powerKW18.3
COP/2.4
Heating IPLV(H)2.7
CoolbNominal capacityKW62
Input powerKW20.7
COP/3
Cooling IPLV(C)2.7
A7W35cKW/COP75.0/4.2
A2W35KW/COP62.5/3.20
A-7W35KW/COP50/2.9
A-15W55KW/COP45.5 /1.97
A-20W45KW/COP37.4/2.04
Max. running currencyA56
Compressor quantityset2
Refrigerant/charging quantity kg/R22/15*2
Air blow type/Top
Water pipe diametermm50
Rating flowm³/h12.6
Water side pressure losskPa≤45
Noise leveldB(A)62
Overall dimensions(L×W×H)mm2100×1100×2080
Weightkg730

a: Nominal heating conditions: ambient dry bulb temperature-12℃, wet bulb temperature-14℃, outlet water temperature 41℃, water flow 0.172 * nominal heating capacity

b:Nominal refrigeration conditions: ambient dry bulb temperature 35℃, outlet water temperature 7℃, water flow 0.172 * nominal cooling capacity

c:A7W35 working condition: inlet air temperature 7℃, outlet water temperature 35℃


YUSHEN Products

  • It could work in extreme environment /Suitable for environmental temperature:-25℃ to +45 ℃ /-13℉ to 113 ℉
  • Quality Components such as Copeland compressor, Danfoss valves
  • 100% finished products testing
  • Having only one unit which could both heat and cool to maintain means lower repair costs and less work in general

Quality 62 DBA Noise Level Heat Pump Heating And Cooling AC ASHP Units With Two Fans for sale
Send your message to this supplier
 
*From:
*To: Shandong Yushen Energy Technology Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0