Model: AC480V-3546KVA
Rated power: 3546 KVA
Voltage: AC480V
PF(Power Factor): 0.8
Display Precision: 0.5 class
Dimension: 6058mm×2438mm×2896mm(L×W×H)
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Grey / Blue 3546 KVA Dummy Load Bank Safety Monitor In High Performance

AC480V-3546KVA Dummy Load Bank In High Performance And Resistive Inductive

Introduction

Triumph load can simulate the real working conditions and provides a rigorous test regime for power supplies from 1kW to 60MW. Resistive, inductive(reactive),capacitive or combined load banks can be customised for any application. They can be used for testing numerous sets in a workshop environment, or used for on-site commissioning, witness tests and proof trials.Tailor-made load banks can be supplied for most powers, voltages, frequencies and sizes. Multi-voltage load banks are also available for operation over a large voltage range. At the same time, It can operate in parallel with more than two units.

Application

AC480V-3546KVA Dummy Load Bank can be used in a wide variety of applications, such as

Ups system testing,Battery system testing,Load optimization in prime power applications

Factory testing of turbines,Factory testing of engine generator sets,To reduce wet stacking problems

Periodic excercising of stand-by engine generator sets

Technical specification


System Parameter
Rating voltage/frequency

480V, 3 phase 3 wire, 60HZ

208V, 3 phase 3 wire, 60HZ

Max Load Power

480V,3phase 3wire, 60HZ, star coupling “Y”

Apparent Power: 3546KVA

Resistive Load: 2836kW

Inductive Load: 2128KVAR

208V,3phase 3wire, 60HZ, delta coupling “△”

Apparent Power: 2000KVA

Resistive Load: 1600kW

Inductive Load: 1200KVAR

Load Resolution

208V,3phase 3wire, 60HZ, delta coupling “△”

Resistive load: 0.1,0.2,0.2,0.5,1,2,2,5,10,10,20,50,100,7*200kW

Inductive load: 0.1,0.2,0.2,0.5,1,2,2,5,10,10,20,50,100,5*200kvar

480V,3phase 3wire, 60HZ, star coupling “Y”

Resistive load: 0.18,0.36,0.36,0.9,1.8,3.6,3.6,9,18,18,36,90,180,7*360kW

Inductive load: 0.18,0.36,0.36,0.9,1.8,3.6,3.6,9,18,18,36,90,180,5*360kvar

Power Factor0.8(lag)
Load Tolerance (each step)±5%
Load Tolerance (overall)±3%
Fan &Control VoltageExternal AC 3 phase 4 line, 380V/50Hz
Wire Connection

Load bank input——Copper bar (star coupling ”Y”)

Control power input——Connector-bar

Communication InterfaceRS485,RS232
InsulationF
Max Protection GradeIP54
Duty CycleContinuous
CoolingForced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling
EnclosureContainer type,with a ladder, air inlet and outlet with mesh enclosure and protection door
Internal LightingAdequate internal lighting will be provided
TransportationHoisting, there are lifting lug in top of casing
ColorGrey RAL7035 or as required
Dimensions6058mm×2438mm×2896mm(L×W×H)
Operating Environment Parameter
WorkplaceOutdoor
Ambient Temperature-10℃~+50℃
Relative Humidity≤95%
Atmospheric Pressure86~106kPa
Brands of Main Components
ContactorSchneider
FuseMiro
PLCSiemens
Alloy ResistorKaixiang
Data Processing SoftwareKaixiang
Main features
Protection Switch: some protection with switch, when misinformation or in special need, user can close the corresponding protection function temporarily.
Safety Monitor: through indicator lights on main interface, user can monitor system state. When system abnormally stop and protect, software interface prompt the cause immediately.

Overvoltage Protection: the input load voltage is over the safe threshold value, system unload automatically and give an alarm.

Short Circuit Protection and Over Current Protection: when short circuit, fuses in the load bank can insure to unload automatically.

Overheating Protection: temperature is over the safe threshold value, system unload automatically and give an alarm.

Smoke Fog Protection: If there is smoke fog in the container, system cut off load automatically and give an alarm.

Fan Delivery Protection: insufficient air volume with any fan 2450m³/h, system unload automatically and give an alarm.

Overload protection with fan: when any fan cannot normally work, the load bank can unload automatically and give an alarm.

Emergency Stop: manually press the Emergency Stop switch on the panel, then load bank is in locked state, and cannot do any operation.