Sign In | Join Free | My frbiz.com |
|
Categories | MV Current Transformer |
---|---|
Brand Name: | Chuangyin |
Model Number: | LZZBJ10-24 |
Certification: | Kema,CE,SGS,TUV |
Place of Origin: | Shenzhen |
MOQ: | 1set |
Payment Terms: | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
Supply Ability: | 36,000,00pcs per year |
Packaging Details: | Plywood |
Rated insulation level: | 24/50/125 kv |
Installation site: | Indoor |
Type: | Epoxy Resin Dry Type |
Material: | Cast |
Ratio: | 15-1500/5 |
Ustage: | Measuring and Protection |
Company Info. |
Shenzhen Chuangyin Co., Ltd. |
Verified Supplier |
View Contact Details |
Product List |
24kv Indoor Single-Phrase Current Transformer Epoxy Resin for
Measuring
1.Product Introduction:
LZZBJ10-17.5/24 current transformer, epoxy resin casting insulation and fully enclosed support construction, encloses primary & secondary windings and annular core in the epoxy resin casting body. The product has the feature of light weight, omnidirectional installation, withstanding nastiness and dampness. It is widely used for measuring current, electric energy and protective relaying in the electrical system with the rated frequency 50- 60Hz and highest voltage for equipment 24kV
2. Technical Data:
Main technical parameter
1. Rated insulation voltage: 24/50/125kV etc.
2. Rated frequency: 50/60hz
3. Installation Site: Indoor
4. Standards: IEC60044-1(IEC61869-1&2)
Two Secondary Single Ratio
Rated transformation ratio(A) | Accuary classes combination | Rated output(VA) | (ALF) | (FS) | Short-time thermal current Ith(kA/S) | Rated dynamic current Idyn(kA) | ||
Measuring | Protective | |||||||
0.2(S) | 0.5 | 10P | ||||||
15/5 …… 200/5 | 0.2(S)/0.2(S) 0.2(S)/0.5 0.5/0.5 0.2(S)/10P 0.5/10P | 10 | 15 | 10 15 | 10 | 5 (10) | 100I1n | 250I1n |
300/5 | 25 | 63 | ||||||
400/5 | 31.5 | 80 | ||||||
500/5 | 40 | 100 | ||||||
600/5 | 40 | 100 | ||||||
800/5 | 63 | 130 | ||||||
1000/5 | 63 | 130 | ||||||
1500/5 | 80 | 160 |
Two Secondary Double Ratio
Rated transformation ratio(A) | Accuary classes combination | Rated output(VA) | (ALF) | (FS) | Short-time thermal current Ith(kA/S) | Rated dynamic current Idyn(kA) | ||
Measuring | Protective | |||||||
0.2(S) | 0.5 | 10P | ||||||
15-30/5 20-40/5 …… 200-400/5 | 0.2(S)/0.2(S) 0.2(S)/0.5 0.5/0.5 0.2(S)/10P 0.5/10P | 10 | 15 | 10 15 | 10 | 5 (10) | 75I1n | 187.5I1n |
300-600/5 | 31.5 | 80 | ||||||
500-1000/5 | 40 | 100 | ||||||
600-1200/5 | 50 | 130 | ||||||
750-1500/5 | 80 | 160 |
![]() |