Sign In | Join Free | My frbiz.com
frbiz.com
Products
Search by Category
Home >

55kw 75hp 220v 380v VFD Variable Frequency Drive Optimal V/F Mode

Categories VFD Variable Frequency Drive
Brand Name: VEIKONG
Model Number: VFD500-055G/075GT4B
Certification: CE, ROHS
Place of Origin: CHINA
MOQ: 1
Price: Please contact quotation
Payment Terms: T/T, Western Union, L/C
Supply Ability: 1000 units per week
Delivery Time: depends on quantities
Packaging Details: <45kw inverter be used carton package, ≥45kw be used wood case package
Voltage: 380v/220v
Power: 55Kw/75hp
Control mode: V/f control, Vector control
Keypad: LED keypad, LCD keypad, Dual display keypad
Warranty: 18 Months
Protection: Overload,Overvoltage,IP20,Short Circuit,over heat
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

55kw 75hp 220v 380v VFD Variable Frequency Drive Optimal V/F Mode

55kw 75hp 220v 380v vector control inverters frequency drive ac drive


Performance Advantage


Advanced motor control algorithm


High performance open loop vector control


Optimal V/F mode


Excellent ramp slope control


Fast auto-tune (less than 1 minute)


Overload: 150% rated output current, 1 minute


Low frequency torque: 0.5Hz: 100% rated torque 1Hz: 150% rated torque


ItemSpecifiation
InputInuput Voltage

1phase/3phase 220V:200V~240V

3 phase 380V-480V:380V~480V

Allowed Voltage fluctuation range-15%~10%
Input frequency50Hz / 60Hz,fluctuation less than 5%
OutputOutput Voltage3phase:0~input voltage
Overload capacity

General purpose application:60S for 150% of the rated current

Light load application:60S for 120% of the rated current

ControlControl mode

V/f control

Sensorless flux vector control without PG card(SVC)

Sensor speed flux vector control with PG card (VC)

Operating modeSpeed control,Torque control(SVC and VC)
Speed range

1:100 (V/f)

1:200( SVC)

1:1000 (VC)

Speed control accuracy

±0.5% (V/f)

±0.2% (SVC)

±0.02% (VC)

Speed response

5Hz(V/f)

20Hz(SVC)

50Hz(VC)

frequency range

0.00~600.00Hz(V/f)

0.00~200.00Hz(SVC)

0.00~400.00Hz(VC)

Input frequency resolution

Digital setting: 0.01 Hz

Analog setting: maximum frequency x 0.1%

Startup torque

150%/0.5Hz(V/f)

180%/0.25Hz(SVC)

200%/0Hz(VC)

Torque control accuracy

SVC:within 5Hz10%,above 5Hz5%

VC:3.0%

V/f curve

V / f curve type: straight line, multipoint, power function, V / f separation;

Torque boost support: Automatic torque boost (factory setting), manual torque boost

Frequency giving ramp

Support linear and S curve acceleration and deceleration;

4 groups of acceleration and deceleration time, setting range 0.00s ~ 60000s

DC bus voltage control

Overvoltage stall control: limit the power generation of the motor by adjusting the output frequency to avoid skipping the voltage fault;


Undervoltage stall control: control the power consumption of the motor by adjusting the output frequency to avoid yaw failure


VdcMax Control: Limit the amount of power generated by the motor by adjusting the output frequency to avoid over-voltage trip;

VdcMin control: Control the power consumption of the motor by adjusting the output frequency, to avoid jump undervoltage fault

Carrier frequency1kHz~12kHz(Varies depending on the type)
Startup method

Direct start (can be superimposed DC brake); speed tracking start


Replace famous brands vfd in general application.


Failure and diagnosis


The VFD500 inverter has perfect protection. If a fault occurs, the inverter will act according to the fault attribute. For more serious faults, the inverter will directly block the output; for general faults, it can be configured to stop or continue to operate according to the scheduled stop mode. After the inverter fails, the fault relay contacts act and the fault code is displayed on the display panel. Before seeking service, users can perform self-checking according to the tips in this section, analyze the cause of the fault, and find a solution.


Fault NameFault codeDisplayPossible CausesSolutions

Inverter unit

protection

1Er. SC

1: motor insulation aging

2: the cable is damaged and contact, short circuit

3:The distance between motor and inverter are too long.

4: output transistor breakdown

5: the internal wiring of the inverter is loose, or the hardware is bad.

6:brake transistor short circuit

1. Confirm the insulation resistance of the motor. If it is turned on, replace the motor.

2. Check the power cable of the motor

3. Install reactor or output filter

4, seeking technical support

5, seeking technical support

6. Check if the braking resistor is damaged and the wiring is correct.

Over current

during

acceleration

2Er.OC1

1: The output circuit is grounded or

short circuited.

2: Motor auto-tuning is not performed.

3: The acceleration time is too short.

4: Manual torque boost or V/F curve is

not appropriate.

5: The voltage is too low.

6: The startup operation is performed

on the rotating motor.

7: A sudden load is added during

acceleration.

8: The frequency inverter model is of

too small power class.

1: Eliminate external faults.

2: Perform the motor auto-

Tuning in cold state

3: Increase the acceleration

time.

4: Adjust the manual torque

boost or V/F curve.

5: Adjust the voltage to normal

range.

6: Select rotational speed

tracking restart or start the

motor after it stops.

7: Remove the added load.

8: Select a frequency inverter

Of higher power class.

Over current

during

deceleration

3Er.OC2

1: The output circuit is grounded or

short circuited.

2: Motor auto-tuning is not performed.

3: The deceleration time is too short.

4: The voltage is too low.

5: A sudden load is added during

deceleration.

6: The braking unit and braking

resistor are not installed

1: Eliminate external faults.

2: Perform the motor

auto-tuning.

3: Increase the deceleration time.

4: Adjust the voltage to normal

range.

5: Remove the added load.

6: Install the braking unit

And braking resistor.

Over current

at constant

speed

4Er.OC3

1: The output circuit is grounded or

short circuited.

2: Motor auto-tuning is notperformed.

3: The voltage is too low.

4: A sudden load is added during

operation.

5: The frequency inverter model is of

too small power class.

1:Eliminate external faults.

2: Perform the motor auto-tuning.

3:Adjust The voltage to normal range.

4: Remove the addedload.

5: Select a frequency

Inverter of higher power class.

Overvoltage

during

acceleration

5Er.OU1

1:the input voltage is too high

2:The surge voltage is mixed in the input power supply.

3: there is an external force to drive the motor to run, or the brake type load is too heavy

4:the acceleration time is too short

5:the motor is shorted to ground

1:the power supply voltage is reduced to the normal range

2:install DC reactor

3:Cancel the external force of the draggable motor or install the brake unit

4: increase the acceleration time

5:eliminate the part of the ground short circuit


Overvoltage

during

deceleration

6Er.OU2

1:the input voltage is too high

2:The surge voltage is mixed in the input power supply.

3: there is an external force to drive the motor to run, or the brake type load is too heavy

4:the decceleration time is too short

5:the motor is shorted to ground

1:the power supply voltage is reduced to the normal range

2:install DC reactor

3:Cancel the external force of the draggable motor or install the brake unit

4: increase the decceleration time

5:eliminate the part of the ground

Overvoltage

at constant

speed

7Er.OU3

1:the input voltage is too high

2:The surge voltage is mixed in the input power supply.

3: there is an external force to drive the motor to run, or the brake type load is too heavy

4:the acceleration or decceleration time is too short

5:the motor is shorted to ground

1:the power supply voltage is reduced to the normal range

2:install DC reactor

3:Cancel the external force of the draggable motor or install the brake unit

4: increase the acceleration or decceleration time

5:eliminate the part of the ground

Low voltage8Er.Lv1

1: Instantaneous power failure occurs

on the input power supply or input phase loss

2: The frequency inverter's input

voltage is not within the allowable

range.

3: cut off the power during operation

4:the internal wiring of the inverter is loose, or the hardware is bad.

1:Check if the input power supply is abnormal, whether the input power terminal is loose, whether the input contactor or the air switch is abnormal.

2:adjust the voltage to the normal range

3:Power off after the inverter stops

4:seeking technical support

5: For the unstable power supply, if the performance requirements are low, try to enable the undervoltage stall function (P23.00).

Contactor open9Er.Lv2

1: Instantaneous power failure occurs

on the input power supply

2: The frequency inverter's input

voltage is not within the allowable

range.

3: cut off the power during operation

4:the internal wiring of the inverter is loose, or the hardware is bad.

1:Check if the input power supply is abnormal, whether the input power terminal is loose, whether the input contactor or the air switch is abnormal.

2:adjust the voltage to the normal range

3:Power off after the inverter stops

4:seeking technical support

5: For the unstable power supply, if the performance requirements are low, try to enable the undervoltage stall function (P23.00).

Frequency

inverter

overload

10Er. oL

1:The load is too large or the motor is blocked.

2:the large inertia load acceleration and deceleration time is too short

3: When the VF is controlled, the torque boost or V/F curve is not suitable.

4:the frequency converter selection is too small

5:overload at low speed operation

1. Reduce the load and check the motor and mechanical conditions.

2, increase the acceleration and deceleration time

3. Adjust the torque boost or V/F curve

4, select the inverter with a larger power level

5. Perform motor self-learning in cold state and reduce carrier frequency at low speed

Motor

overload

11Er.oL1

1:The load is too large or the motor is blocked.

2:the large inertia load acceleration and deceleration time is too short

3:When the VF is controlled, the torque boost or V/F curve is not suitable.

4:the motor selection is too small

5:overload at low speed operation

6:Improper setting of motor parameters and motor protection parameters

1. Reduce the load and check the motor and mechanical conditions. Correctly set the motor parameters and motor protection parameters.

2, increase the acceleration and deceleration time

3. Adjust the torque boost or V/F curve

4, select a motor with a higher power level

5. Perform motor self-learning in cold state and reduce carrier frequency at low speed

6, check the settings of related parameters