MTL4513 Switch/ Proximity Detector Interface 2-Channel, Line Fault Detection, Phase Revers

Categories MTL4500 Series Safety Barriers
Place of Origin: UK
Brand Name: MTL
Certification: CE
Model Number: MTL4513
MOQ: 10 Pcs
Packaging Details: carton
Delivery Time: approx. 4 weeks
Payment Terms: T/T payment
Supply Ability: 300 pcs
Price: according to the purchase quantity
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
  • Submit Buying Request
    • Product Details
    • Company Profile

    MTL4513 Switch/ Proximity Detector Interface 2-Channel, Line Fault Detection, Phase Revers

    MTL4513 Switch/ Proximity Detector Interface 2-Channel, Line Fault Detection, Phase Reversal

    MTL4513 enables two solid-state outputs in the safe area to be controlled by two switches or proximity detectors located in the hazardous area. The Ch1/Ch2 output transistors share a common terminal and can switch +ve or -ve polarity signals. Independent output phase reversal and line fault detection are enabled via switches for each output. LFD indication is provided on the top of the module.

    SPECIFICATION FOR MTL4513

    See also common specification

    Number of channels

    Two

    Location of switches

    Zone 0, IIC, T6 hazardous area

    Div. 1, Group A hazardous location

    Location of proximity detectors

    Zone 0, IIC, T4–6 hazardous area if suitably certified

    Div. 1, Group A hazardous location

    Hazardous-area inputs

    Inputs conforming to BS EN60947–5–6:2001 standards for

    Proximity detectors (NAMUR)

    Voltage applied to sensor

    7 to 9V dc from 1kΩ ±10%

    Input/output characteristics

    Normal phase

    Outputs closed if input > 2.1mA (< 2kΩ in input circuit)

    Outputs open if input < 1.2mA (> 10kΩ in input circuit)

    Hysteresis: 200µA (650Ω) nominal

    Line fault detection (LFD) (when selected)

    User-selectable for each channel via switches on the side of the unit. Line faults are indicated by an LED for each channel.

    Open-circuit alarm on if Iin < 50µA

    Open-circuit alarm off if Iin > 250µA

    Short-circuit alarm on if Rin < 100Ω

    Short-circuit alarm off if Rin > 360Ω

    Note: Resistors must be fitted when using the LFD facility with a contact input

    500Ω to 1kΩ in series with switch

    20kΩ to 25kΩ in parallel with switch

    Phase reversal

    Independent for each channel, user-selectable

    Safe-area outputs

    Floating solid-state outputs compatible with logic circuits

    Operating frequency: dc to 500Hz

    Max. off-state voltage: ± 35V

    Max. off-state leakage current: ± 50µA

    Max. on-state resistance: 25Ω

    Max. on-state current: ± 50mA


    Functional Safety Management (FSM)

    Many MTL products are certified as safe for use in hazardous areas; that is places where explosive material may be present. The products are designed and certified to show that they are incapable of igniting the gas or dust and causing fire or explosion.

    Another type of safety is called Functional Safety, which applies when products are used in safety and protection systems, in which a failure may mean that a protective system will not operate as it should. MTL products have been used in safety systems for some time, but there are increasing requirements to demonstrate an adequate level of functional safety, especially after the Buncefield, Texas City and Deepwater Horizon accidents. More and more, customers are demanding that products they use in safety systems meet the requirements of the second edition of the IEC 61508 Functional Safety standard, and they require evidence to show that they do. This is to enable the use of our products within instrumentation loops that are designed to achieve a specific Safety Integrity Level (SIL).

    When MTL designs a product in the expectation that it will be used in functional safety-related systems, both the design process and the product needs to comply with IEC 61508:2010.

    MTL has chosen to obtain Functional Safety Management (FSM) certification for the company. FSM means that MTL has the necessary processes and competence to design products according to IEC 61508:2010. Certification means that a notified body is ensuring that our processes are correct and that we are working to them. Together, FSM Certification gives our customers confidence in the company and the use of our products for functional safety.



    Contact E-mail: info@mtl-instruments.com; mtl_inst@yeah.net

    Contact Person: Mr. Steven

    Quality MTL4513 Switch/ Proximity Detector Interface 2-Channel, Line Fault Detection, Phase Revers for sale